Physical
–
o
Dimensions:
8
inches x 10 inches x 6.5 inches
o
Mounting:
Bulkhead
o
Enclosure:
NEMA 4X, Fiberglass
o
Connections:
§
RS-232, Female 9 Pin Subminiature D connector
§
Power, Analog, Digital I/O, Wire Range 28 – 14 AWG
§
Antenna, Reverse-polarity SMA (Whip antenna included)
o
Indicators (SSR):
§
Fail (Red)
§
Power / Transmit activity (Green).
§
Radio Receive activity (Yellow)
§
TX (Yellow) activity. RS232 or RS485
§
RX (Yellow) activity. RS232 or RS485
§
RS232 Mode
§
RS485 Mode
o
Indicators (DC:
§
Fail (Red)
§
Power (Green).
§
TX (Yellow) activity. 1 per RS232/RS485 (3 Total)
§
RX (Yellow) activity. 1 per RS232/RS485 (3 Total)
§
Ethernet Link
§
Ethernet Activity
Electrical (PS) –
o
Supply Voltage: 85/285 VAC, 47/440 HZ
o
Transient Protection:
AC Line Protection Included
Electrical (SSR) –
o
Current draw:
Receive 70 mA, Transmit 140 mA max
o
Frequency:
902-928 MHz
o
Modulation Type:
Spread Spectrum, Frequency Hopping Wide band FM.
o
Channel Capacity: 7 hop sequences sharing 25 frequencies.
o
Transmit Power:
140 mW.
o
Receiver Sensitivity: -110 dbm
o
RS232/RS485 baud rate:
9600 Default, 1200 – 57600
o
RF Data Rage:
9600 baud, Fixed.
o
Receive Buffer Size: 16 bytes.
o
Flow Control:
(RS232 Only) RTS/CTS Enabled, Default
Range –
NOTE:
Ranges specified are typical. Actual range
will depend on several factors including antenna type,
distance above ground, and presence of obstructions. (Yagi
and Omni antenna may be purchased separately)
o
Indoor:
1500 Feet
o
Outdoor, Line of Sight: 7 – 20 Miles
Electrical (DC) –
o
Analog Inputs:
§
4/20 mADC via 250 Ohm resistor, 1-5 VDC
§
Resolution 12 bits
o
Analog Outputs:
§
4/20 mADC
§
Resolution 12 bits
o
Digital Inputs:
Dry contact closure
o
Digital Outputs:
Dry contacts, 0.3A @ 125VAC, 0.5 A @ 30 VDC
o
RS232/RS485 baud rate:
9600 Default, 1200, 19200
o
Ethernet:
10baseT
o
CPU:
Industrial Hardened Microcontroller
·
Real Time Clock: Perpetual
Software (DC) -
o
Supported Protocols:
§
HTTP
§
SMTP
§
FTP
§
Telnet
§
AGM Data Handler (DH)
§
AGM Integrated Control Station (ICS)
§
Modbus(ASCII/RTU/TCP/IP)
§
DF1, Half-Duplex
§
DNP
§
ASCII
o
Features:
§
Web Server
§
Built-in Pages
§
Custom Pages
§
Display selected data
§
Messaging/E-Mail
§
Periodically
§
Event
§
Configuration
§
Locally
§
Remotely via Ethernet HTTP connection and standard web
browsers
§
FTP - Download custom pages or messages
§
Real Time Clock - Date and time stamp of activity
§
Memory - 1 Megabyte Flash memory for configuration,
custom web pages and messages
Configuration -
o
Custom WEB Page Titles:
Up to 3 lines
o
Date and time:
§
Setting
§
Display format
o
Security settings:
§
One master administrator
§
Up to 3 alternate users
o
Addressing:
§
IP Address
§
Subnet mask
§
TCP
Port
o
TCP/IP Port Assignment Protection:
Changes will be confirmed by reconnecting within
specified period of time.
o
Protocols:
Individually selectable for each of the 2 ports
o
Baud rates: Individually selectable for each of the 2 ports (300, 1200, 9600,
and 19200 supported)
o
Data Display: Selected variables are also available for HTML pages
o
E-Mail address, SMTP server: messaging interval and one alarm value may be set
o
Configuration Interface:
§
Settings configured via HTML pages
§
Custom web pages downloaded via FTP
§
Custom E-Mail page downloaded via FTP
§
Configuration may be saved or restored via FTP
§
Configuration may be cloned via FTP
o
Ports Interface:
§
Port A, RS-232
§
Port B, RS-232
§
Port 4, RS-485
§
Port T, Ethernet TCP/IP
o
Messaging:
§
Built in message displays single user selectable value
§
Custom message can display any or all of the 32 defined
translation values
§
Message may be initiated on a user defined interval or
event
§
Single value only
Environmental -
o Operating
Temperature:
-30 to 80 degrees C
o Operating
Humidity:
5 to 95%
Warranty –
o 7
years, Transferable |