Physical -
o
Dimensions:
3
inches x 1.4 inches x 2.7 inches (AUX)
3
inches x 1.4 inches x 3.5 inches (DIN)
o
Mounting: Bulkhead, DIN
o
Connections:
§
RS-232, Male 9 Pin Subminiature D connector
§
RS-232, RS-485, Female 9 Pin Subminiature D connector. RS-232 /
RS-485 software selectable
§
Power, Analog, Digital I/O, Wire Range 28 – 14 AWG
§
Ethernet, RJ45
o
Indicators:
§
Fail (Red)
§
Power (Green).
§
TX (Yellow) activity. 1 per RS232/RS485 (3 Total)
§
RX (Yellow) activity. 1 per RS232/RS485 (3 Total)
§
Ethernet Link
§
Ethernet Activity
·
Electrical -
o
Supply Voltage: 11 to 26 VDC
o
Current draw:
Nominal 250 mA max
o
Analog Inputs:
§
4/20 mADC via 250 Ohm resistor, 1-5 VDC
§
Resolution 12 bits
o
Analog Outputs:
§
4/20 mADC
§
Resolution 12 bits
o
Digital Inputs:
Dry contact closure.
o
Digital Outputs:
Dry contacts.
o
RS232/RS485 baud rate:
9600 Default, 1200, 19200
o
Ethernet:
10baseT
o
CPU:
Industrial Hardened Microcontroller
o
Real Time Clock:
Perpetual
·
Software -
o
Supported Protocols:
§
HTTP
§
SMTP
§
FTP
§
Telnet
§
AGM Data Handler (DH)
§
AGM Integrated Control Station (ICS)
§
Modbus(ASCII/RTU/TCP/IP)
§
DF1, Half-Duplex
§
DNP
§
ASCII
o
Features:
§
Web Server
§
Built-in Pages
§
Custom Pages
§
Display selected data
§
Messaging/E-Mail
§
Periodically
§
Event
§
Configuration
§
Locally
§
Remotely via Ethernet HTTP connection and standard web
browsers
§
FTP - Download custom pages or messages
§
Real Time Clock - Date and time stamp of activity
§
Memory - 1 Megabyte Flash memory for configuration,
custom web pages and messages
·
Configuration -
o
Custom WEB Page Titles:
Up to 3 lines
o
Date and time:
§
Setting
§
Display format
o
Security settings:
§
One master administrator
§
Up to 3 alternate users
o
Addressing:
§
IP Address
§
Subnet mask
§
TCP Port
o
TCP/IP Port Assignment Protection:
Changes will be confirmed by reconnecting within
specified period of time.
o
Protocols: Individually selectable for each of the 2 ports
o
Baud rates: Individually selectable for each of the 2 ports
(300, 1200, 9600, and 19200 supported)
o
Data Display: Selected variables are also available for HTML
pages
o
E-Mail address, SMTP server:
messaging interval and one alarm value may be set
o
Configuration Interface:
§
Settings configured via HTML pages
§
Custom web pages downloaded via FTP
§
Custom E-Mail page downloaded via FTP
§
Configuration may be saved or restored via FTP
§
Configuration may be cloned via FTP
o
Ports Interface:
§
Port A, RS-232
§
Port B, RS-232
§
Port 4, RS-485
§
Port T, Ethernet TCP/IP
o
Messaging:
§
Built in message displays single user selectable value
§
Custom message can display any or all of the 32 defined translation
values
§
Message may be initiated on a user defined interval or event
§
Single value only
·
Environmental -
o
Operating Temperature:
-30 to 80 degrees C
o
Operating Humidity: 5 to 95%.
·
Warranty –
o