Description –
The Track and Hold accepts a 4/20 mADC signal
and a Contact Closure. The output of the Track
and Hold will Track the input as long as the
Contact Closure is open. When the Contact is
closed, the output of the Track and Hold will
freeze and hold the output to the signal level
when the Contact was closed. When the Contact is
opened, the output of the Track and Hold will
resume Tracking the input signal.
The Track and Hold

Specifying/Ordering –
Product Application Number (PAN)
SF8
Specifications –
E – NEMA 1 Rated Enclosure
P – 115 VAC, 60 Hz
I1 – Input 1 – 4/20 mADC, Z = 50 Ohms
I2 – Input 2 – Dry Contact
O – Output – 4/20 mADC, 550 Ohms Drive
Use the following table to specify other
options.
|
|
E |
P |
|
A |
NEMA 4 |
220 VAC, 50/60 Hz |
|
B |
DIN |
24 VDC |
Example – SF8–EB-PB
Resulting Specifications –
E – DIN Rail Mounting
P – 24 VDC
I1 – Input 1 – 4/20 mADC, Z = 50 Ohms
I2 – Input 2 – Dry Contact
O – Output – 4/20 mADC, 550 Ohms Drive
|