Description –
The Rate Limiter accepts a 4/20 MADC signal
and provides a 4/20 mADC output signal that
is limited to that rate at which it can
change. The Rate of Change is adjustable
from 0/60 seconds. For example, if the Rate
of Change is set to 30 seconds, it will take
30 seconds for the output to go from 4 to 20
mADC based on an input signal step change of
4 to 20 mADC.

Specifying/Ordering –
Product Application Number (PAN)
SF12
Specifications –
E – NEMA 1 Rated Enclosure
P – 115 VAC, 60 Hz
I – Input – 4/20 mADC, Z = 50 Ohms
O – Output – 4/20 mADC, 550 Ohms Drive
Rate of Change Limiting adjustable from 0 to 60 seconds
Use the following table to specify other
options.
|
|
E |
P |
|
A |
NEMA 4 |
220 VAC, 50/60 Hz |
|
B |
DIN |
24 VDC |
Example – SF12–EB-PB
Resulting Specifications –
E – DIN Rail Mounting
P – 24 VDC
I – Input – 4/20 mADC, Z = 50 Ohms
O – Output – 4/20 mADC, 550 Ohms Drive
Rate of Change Limiting adjustable from 0 to 60 seconds