Description –
The Data Handler (DH) at the local site accepts
a 4/20 mADC tank level signal and compares it to
internal turn on and turn off setpoints. The DH,
in turn, transmits pump on and off commands to
the remote site DH via the leased line/dial-up
modems. The remote DH converts those commands to
contact outputs for operating the motor starter.
The remote site DH accepts one 4/20 mADC pump
flow signal and pump running contacts and
transmits them to the local site and converts
them back to 4/20 mADC and contact closure for
local display and recording. The local site DH
closes a contact in the event there is a
communications failure.

Specifying/Ordering –
Product Application Number (PAN)
DLS6
Specifications –
E – NEMA 1 Rated Enclosures
P – Power – 115 VAC, 60 Hz,
I1 – Input Analogs – 1 each 4/20 mADC, Z = 250 Ohms
O1 – Output Analogs – 1 each 4.20 mADC
I2 – Input Contact Closures – 2 each Dry
O2 – Output Contact Closures – 2 each
Use the following table to specify other
options.
|
|
E |
P |
|
A |
NEMA 4 |
220 VAC, 50/60 HZ |
|
B |
|
24 VDC |
Example – DLS6–EA-PB
Resulting Specifications –
E – NEMA 4 Rated Enclosures
P – Power – 24 VDC
|