Description –
The Controller compares the 4/20mADC Level
signal to an adjustable on and off setpoint. The
Controller contact closure output connects to
the Supervisory Transmitter which is connected
to a dry wire pair. The Supervisory Transmitter
transmits the signal to the Supervisory
Receiver. The Supervisory Receiver receives and
converts the signal to a dry contact closure
which is used to operate a pump starter.
The
Supervisory Receiver accepts a pump running
contact and transmits it back to the Supervisory
Transmitter. The Supervisory Transmitter
provides a contact output that is used to
operate Pump Status indicators. This application
is used to maintain a level in a tank. Also, the
Supervisory Transmitter will turn both Pump
Status indicators on in the event there is a
communication fault.

Specifying/Ordering –
Product Application Number (PAN)
DLS5
Specifications –
E – NEMA 1 Rated Enclosures
P – Power – 115 VAC, 60 Hz
I – Input – 4/20 mADC, Z = 50 Ohms, Pump Up
O – Output – Dry Contact – Pump Status
Use the following table to specify other
options.
|
|
E |
P |
I |
|
A |
NEMA 4 |
220 VAC, 50/60 HZ |
4/20 mADC, Z = 50 Ohms, Pump Down |
|
B |
|
24 VDC |
|
Example – DLS5–EA-PB-IA
Resulting Specifications –
E – NEMA 4 Rated Enclosures
P – Power – 24 VDC
I – Input – 4/20 mADC, Z = 50 Ohms, Pump Down
|