Signal Conditioning | Monitoring | Control Communication | Data Handling | Interface

 

DLS4 – Leased/Dedicated Line Analog Signal Transceiver with Level/Alarm Controller

 
 

Description –

 

The Pulse Duration Transmitter converts a 4/20 mADC signal to a periodic proportional modulated pulse width contact closure that is connected to a dry wire pair. A Pulse Duration Receiver is connected to the other end of the dry wire pair.

 

It detects the modulated contact closure and converts it back to a 4/20mADC signal.

 

The 4/20 mADC signal may be connected to a local display, chart recorder or PLC.

 

The 4/20 mADC is also connected to the Controller which compares the 4/20mADC to an adjustable on and off setpoint. The Controller contact closure output can be used to operate a pump to maintain the level in the Tank or operate a level alarm.

 

 

Specifying/Ordering –

 

Product Application Number (PAN)

 

DLS4

 

Specifications –

            E – NEMA 1 Rated Enclosures

P – Power – 115 VAC, 60 Hz,

I – Input – 4/20 mADC, Z = 50 Ohms

M – PDM Format – 3/12 Sec, 15 Sec Period, up to 3000 Ohms Line Resistance

O1 – Output 1 – 4/20 mADC, Drive = 550 Ohms

O2 – Output 2 – Pump Up

 

  

Use the following table to specify other options.

 

 

E

P

I

M

O1

O2

A

NEMA 4

220 VAC, 50/60 HZ

1/5 VDC

0/13.33, 15 Sec

1/ 5 VDC

Pump Down

B

 

24 VDC

0/10 VDC

0/53.33,  60 Sec

0/10 VDC

 

 

Example – DLS4–EA-PB-IA-MA-O1B-O2A

 

Resulting Specifications –

            E – NEMA 4 Rated Enclosures

P – Power – 24 VDC

I1 – Input – 1/5VDC

M – PDM Format – 0/13.33 Sec, 15 Sec Period, up to 3000 Ohms Line Resistance

O1 – Output – 0/10 VDC

                        O2 – Pump Down

 

 

"Wireless TransCeiver (WTC)"

"Telephone Lines are for the Birds"

As leased dedicated phone lines are becoming more difficult to acquire, AGM customers are switching to wireless data communications using AGM's Data Handlers (DH) and Spread Spectrum Radios (SSR).

"Beep Alert"

The Data Handler, when combined with your existing  pager system, provides a convenient, low cost way to detect and broadcast remote site alarms such as a pump failure or unauthorized intrusion.

"AWT"

Erratic flow signals can result in unnecessary wear and tear on chemical feed equipment.

Use the Data Handler application, "Average with Time", to smooth the signal.

 