Description –
The Pulse Duration Transmitter converts a 4/20
mADC signal to a periodic time modulated
pulse width contact closure that is connected to
a dry wire pair. A Pulse Duration Receiver is
connected to the other end of the dry wire pair. It
detects the time modulated contact closure and
converts it back to a 4/20mADC signal.
The 4/20
mADC signal may be connected to a local display,
chart recorder or PLC.
The 4/20 mADC is also
connected to the Intergator which converts the
4/20mADC to a proportional contact closure pulse
rate which may be used to drive a totalizer,
pulse a chemical feeder or
be connected to a PLC.

Specifying/Ordering –
Product Application Number (PAN)
DLS1
Specifications –
E – NEMA 1 Rated Enclosures
P – Power – 115 VAC, 60 Hz,
I – Input – 4/20 mADC, Z = 50 Ohms
M – PDM Format – 3/12 Sec, 15 Sec Period, up to
3000 Ohms Line Resistance
O1 – Output 1 – 4/20 mADC, Drive = 550 Ohms
O2 – Output 2 – 0/10 Pulses per Minute, Contact
Closure
Use the following table to specify other
options.
|
|
E |
P |
I |
M |
O1 |
O2 |
|
A |
NEMA 4 |
220 VAC, 50/60 HZ |
1/5 VDC |
0/13.33, 15 Sec |
1/ 5 VDC |
Specify |
|
B |
|
24 VDC |
0/10 VDC |
0/53.33, 60 Sec |
0/10 VDC |
|
Example – DLS1–EA-PB-IA-IMA-O1B-0/100PPM
Resulting Specifications –
E – NEMA 4 Rated Enclosures
P – Power – 24 VDC
I – Input – 1/5VDC
M – PDM Format – 0/13.33 Sec, 15 Sec Period, up
to 3000 Ohms Line Resistance
O1 – Output 1 – 0/10 VDC
O2 – Output 2 – 0/100 PPM, Contact Closure |