Description –
The AXB accepts a 3-Wire Potentiometer and a
4/20 mADC Flow Signal and multiplies the 2
signals together which results in a scaled 4/20
mADC signal. The Potentiometer is adjusted so
that the Chemical Pump provides an appropriate
amount of chemical that is proportional to the
changing Flow Signal.

Specifying/Ordering –
Product Application Number (PAN)
MF3
Specifications –
E – NEMA 1 Rated Enclosure
P – 115 VAC, 60 Hz
I1 – Input 1 – 3-Wire Potetentiomer, 0/20K Ohms
w/ DIal
I2 – Input 2 – 4/20 mADC – Z = 50 Ohms
O – Output – 4/20 mADC, 550 Ohms drive
Use the following table to specify other
options.
|
|
E |
P |
|
A |
NEMA 4 |
220 VAC, 50/60 Hz |
|
B |
DIN |
24 VDC |
Example – MF6–EA-PA
Resulting Specifications –
E – NEMA 4 Rated Enclosure
P – 220 VAC, 50/60 Hz
|