Description –
The AXB Multiplier accepts a 4/20 mADC flow
signal and 2 each 100 Ohm Platinum RTD connected
differentially and multiplies the delta T across
the heat exchanger and the flow. The result is a
4/20 mADC signal that corresponds to BTU’s or
the rate of heat energy transfer.

Specifying/Ordering –
Product Application Number (PAN)
MF1
Specifications –
E – NEMA 1 Rated Enclosure
P – 115 VAC, 60 Hz
I1 – Input 1 – 4/20 mADC – Z = 50 Ohms
I2 – Input 2 – 2 each 100 Ohms Platinum RTD
connected differentially, 0/20 Deg C
O – Output – 4/20 mADC, 550 Ohms drive
Use the following table to specify other
options.
|
|
E |
P |
|
A |
NEMA 4 |
220 VAC, 50/60 Hz |
|
B |
DIN |
24 VDC |
Example – MF2–EA-PA
Resulting Specifications –
E – NEMA 4 Rated Enclosure
P – 220 VAC, 50/60 Hz
Note –
See PAN MF7 for Totalizing BTUs
|